案例1:
下表是某实际工程的桥架填充率计算书,电缆单排并列宽度为442mm,桥架选用300 mm(宽)x200 mm(高)。填充率为26.79%,满足不大于40%的规范要求。
桥架填充率计算书 |
序号 | 电缆截面积 | 各类电缆半径 | 各类电缆面积和 | 各类电缆横排所需宽度 |
3+1c | 3+2c | 4+1c | 3c | 4c | 5c |
电缆直径 | 根数 | 电缆直径 | 根数 | 电缆直径 | 根数 | 电缆直径 | 根数 | 电缆直径 | 根数 | 电缆直径 | 根数 |
1 | 4 | 13.4 |
| 14.3 |
| 14.5 |
|
|
| 13.7 |
| 14.8 |
| 0 | 0 |
2 | 6 | 14.6 |
| 15.6 |
| 15.9 |
|
|
| 14.9 |
| 16.1 |
| 0 | 0 |
3 | 10 | 17.3 |
| 18.4 |
| 18.9 |
|
|
| 48 |
| 19.6 |
| 0 | 0 |
4 | 16 | 20 |
| 21.4 |
| 21.9 |
|
|
| 20.6 |
| 22.4 |
| 0 | 0 |
5 | 25 | 23.8 |
| 25.4 |
| 26.2 |
|
|
| 24.8 |
| 27.2 |
| 0 | 0 |
6 | 35 | 25.8 |
| 27.5 |
| 28.8 |
|
|
| 27.6 |
| 30.5 |
| 0 | 0 |
7 | 50 | 29.9 |
| 32.1 |
| 33.4 | 2 |
|
| 31.6 |
| 35 |
| 1751.429 | 66.8 |
8 | 70 | 34.6 |
| 37.1 |
| 38.8 | 4 |
|
| 36.8 |
| 40.8 |
| 4727.082 | 155.2 |
9 | 95 | 39.3 |
| 42.2 |
| 44.1 |
|
|
| 41.8 |
| 46.4 |
| 0 | 0 |
10 | 120 | 44.2 |
| 47.7 |
| 49.5 | 2 |
|
| 46.5 |
| 51.7 |
| 3846.893 | 99 |
11 | 150 | 48 |
| 51.4 |
| 54..1 |
|
|
| 51.6 |
| 57.4 |
| 0 | 0 |
12 | 185 | 53.8 |
| 57.7 |
| 60.5 | 2 |
|
| 57.6 |
| 64.1 |
| 5746.593 | 121 |
13 | 240 | 60.5 |
| 64.9 |
| 68.2 |
|
|
| 64.9 |
| 72.3 |
| 0 | 0 |
14 | 300 | 66.9 |
| 74 |
| 75.1 |
|
|
| 71.8 |
| 80 |
| 0 | 0 |
总的电缆面积和/根数 |
|
|
|
|
|
| 16072 | 10 |
所需桥架截面面积(40%计算) |
|
|
|
|
|
| 40179.99 |
|
电缆横排所需总宽度(注:电缆是相邻紧贴排列) |
|
|
|
|
|
|
| 442 |
设计桥架规格 | 300 | 200 |
|
|
|
|
|
|
|
|
| 60000 | 0.267866597 |
上述做法好像是没有问题。实际存在一个较为严重的隐患。
根据《电力工程电缆设计标准》GB50217-2018附录D的表D.0.6多层并列电缆在托盘桥架上敷设时校正系数取值。
电缆桥架上无间距配置多层并列电缆载流量的校正系数见下表 表D.0.6 电缆桥架上无间距配置多层并列电缆载流量的校正系数 |
叠置电缆层数 | 1 | 2 | 3 | 4 |
桥架类别 | 桥架 | 0.8 | 0.65 | 0.55 | 0.5 |
托盘 | 0.7 | 0.55 | 0.5 | 0.45 |
注:呈水平状并列电缆数不少于7根。 |
可以看出电缆在桥架上单层并列敷设时,校正系数取0.7,两层并列敷设时校正系数取0.55。从经济性考虑,工程设计时通常都是按照单层敷设情况下取校正系数0.7。因此在选择桥架时,桥架的宽度必须大于电缆单排并列宽度。
本案例中电缆单排并列宽度442mm,桥架宽度300mm,导致部分电缆在桥架中是两层并列敷设。如果要保证电缆安全使用,其载流量的校正系数按照0.55取,实际工程是按照0.7选取,因而造成电缆过载。其结果是电缆散热不利,绝缘老化加速,电缆的使用寿命会大大折减,并存在用电安全隐患。
选择电缆桥架规格时,满足填充率的前提下,还需要保证桥架宽度大于电缆单层并列宽度。